Der Sensor meldet als Alarm die Zahlenfolge 1.3.6.1.2.1.33.1.6.3.2 (als Beispiel!) - was bedeutet das?
Lösung:
Alarme werden in der Eaton als SNMP-OIDs wiedergegeben. Diese OIDs haben folgende feste Bedeutung, basierend auf der UPS-MIB.mib:
OID | interner Name | Bedeutung |
---|---|---|
1.3.6.1.2.1.33.1.6.3.1 | upsAlarmBatteryBad | One or more batteries have been determined to require replacement. |
1.3.6.1.2.1.33.1.6.3.2 | upsAlarmOnBattery | The UPS is drawing power from the batteries. |
1.3.6.1.2.1.33.1.6.3.3 | upsAlarmLowBattery | The remaining battery run-time is less than or equal to upsConfigLowBattTime. |
1.3.6.1.2.1.33.1.6.3.4 | upsAlarmDepletedBattery | The UPS will be unable to sustain the present load when and if the utility power is lost. |
1.3.6.1.2.1.33.1.6.3.5 | upsAlarmTempBad | A temperature is out of tolerance. |
1.3.6.1.2.1.33.1.6.3.6 | upsAlarmInputBad | An input condition is out of tolerance. |
1.3.6.1.2.1.33.1.6.3.7 | upsAlarmOutputBad | An output condition (other than OutputOverload) is out of tolerance. |
1.3.6.1.2.1.33.1.6.3.8 | upsAlarmOutputOverload | The output load exceeds the UPS output capacity. |
1.3.6.1.2.1.33.1.6.3.9 | upsAlarmOnBypass | The Bypass is presently engaged on the UPS. |
1.3.6.1.2.1.33.1.6.3.10 | upsAlarmBypassBad | The Bypass is out of tolerance. |
1.3.6.1.2.1.33.1.6.3.11 | upsAlarmOutputOffAsRequested | The UPS has shutdown as requested, i.e., the output is off. |
1.3.6.1.2.1.33.1.6.3.12 | upsAlarmUpsOffAsRequested | The entire UPS has shutdown as commanded. |
1.3.6.1.2.1.33.1.6.3.13 | upsAlarmChargerFailed | An uncorrected problem has been detected within the UPS charger subsystem. |
1.3.6.1.2.1.33.1.6.3.14 | upsAlarmUpsOutputOff | The output of the UPS is in the off state. |
1.3.6.1.2.1.33.1.6.3.15 | upsAlarmUpsSystemOff | The UPS system is in the off state. |
1.3.6.1.2.1.33.1.6.3.16 | upsAlarmFanFailure | The failure of one or more fans in the UPS has been detected. |
1.3.6.1.2.1.33.1.6.3.17 | upsAlarmFuseFailure | The failure of one or more fuses has been detected. |
1.3.6.1.2.1.33.1.6.3.18 | upsAlarmGeneralFault | A general fault in the UPS has been detected. |
1.3.6.1.2.1.33.1.6.3.19 | upsAlarmDiagnosticTestFailed | The result of the last diagnostic test indicates a failure. |
1.3.6.1.2.1.33.1.6.3.20 | upsAlarmCommunicationsLost | A problem has been encountered in the communications between the agent and the UPS. |
1.3.6.1.2.1.33.1.6.3.21 | upsAlarmAwaitingPower | The UPS output is off and the UPS is awaiting the return of input power. |
1.3.6.1.2.1.33.1.6.3.22 | upsAlarmShutdownPending | A upsShutdownAfterDelay countdown is underway. |
1.3.6.1.2.1.33.1.6.3.23 | upsAlarmShutdownImminent | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. |
1.3.6.1.2.1.33.1.6.3.24 | upsAlarmTestInProgress | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanism… |