Der Sensor meldet als Alarm die Zahlenfolge 1.3.6.1.2.1.33.1.6.3.2 (als Beispiel!) - was bedeutet das?


Lösung:

Alarme werden in der Eaton als SNMP-OIDs wiedergegeben. Diese OIDs haben folgende feste Bedeutung, basierend auf der UPS-MIB.mib:


OIDinterner NameBedeutung
1.3.6.1.2.1.33.1.6.3.1upsAlarmBatteryBad

One or more batteries have been determined to require

replacement.

1.3.6.1.2.1.33.1.6.3.2upsAlarmOnBatteryThe UPS is drawing power from the batteries.
1.3.6.1.2.1.33.1.6.3.3upsAlarmLowBatteryThe remaining battery run-time is less than or equal

to upsConfigLowBattTime.

1.3.6.1.2.1.33.1.6.3.4upsAlarmDepletedBattery

The UPS will be unable to sustain the present load

when and if the utility power is lost.

1.3.6.1.2.1.33.1.6.3.5upsAlarmTempBadA temperature is out of tolerance.
1.3.6.1.2.1.33.1.6.3.6upsAlarmInputBadAn input condition is out of tolerance.
1.3.6.1.2.1.33.1.6.3.7upsAlarmOutputBad

An output condition (other than OutputOverload) is

out of tolerance.

1.3.6.1.2.1.33.1.6.3.8upsAlarmOutputOverloadThe output load exceeds the UPS output capacity.
1.3.6.1.2.1.33.1.6.3.9upsAlarmOnBypassThe Bypass is presently engaged on the UPS.
1.3.6.1.2.1.33.1.6.3.10upsAlarmBypassBadThe Bypass is out of tolerance.
1.3.6.1.2.1.33.1.6.3.11upsAlarmOutputOffAsRequested

The UPS has shutdown as requested, i.e., the output

is off.

1.3.6.1.2.1.33.1.6.3.12upsAlarmUpsOffAsRequestedThe entire UPS has shutdown as commanded.
1.3.6.1.2.1.33.1.6.3.13upsAlarmChargerFailed

An uncorrected problem has been detected within the

UPS charger subsystem.

1.3.6.1.2.1.33.1.6.3.14upsAlarmUpsOutputOffThe output of the UPS is in the off state.
1.3.6.1.2.1.33.1.6.3.15upsAlarmUpsSystemOffThe UPS system is in the off state.
1.3.6.1.2.1.33.1.6.3.16upsAlarmFanFailure

The failure of one or more fans in the UPS has been detected.

1.3.6.1.2.1.33.1.6.3.17upsAlarmFuseFailureThe failure of one or more fuses has been detected.
1.3.6.1.2.1.33.1.6.3.18upsAlarmGeneralFaultA general fault in the UPS has been detected.
1.3.6.1.2.1.33.1.6.3.19upsAlarmDiagnosticTestFailed

The result of the last diagnostic test indicates a failure.

1.3.6.1.2.1.33.1.6.3.20upsAlarmCommunicationsLost

A problem has been encountered in the communications

between the agent and the UPS.

1.3.6.1.2.1.33.1.6.3.21upsAlarmAwaitingPower

The UPS output is off and the UPS is awaiting the

return of input power.

1.3.6.1.2.1.33.1.6.3.22upsAlarmShutdownPendingA upsShutdownAfterDelay countdown is underway.
1.3.6.1.2.1.33.1.6.3.23upsAlarmShutdownImminent

The UPS will turn off power to the load in less than

5 seconds; this may be either a timed shutdown or a

low battery shutdown.

1.3.6.1.2.1.33.1.6.3.24upsAlarmTestInProgress

A test is in progress, as initiated and indicated by

the Test Group. Tests initiated via other

implementation-specific mechanism…